E3G080 Control Module "Extinguishing - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3G080 Control module "Extinguishing"

37
E3G080 Control module "Extinguishing"
37.1
Overview
37.2
Application
150
Building Technologies
Fire Safety & Security Products
E3G080 > Index 'CC' compatible with EP5 onwards
E3G080 > Index 'AB' compatible with EP4 onwards
E3G080 < Index 'AB' is only compatible with EP3a (further details refer to MI220)
I-Bus module as control module for one extinguishing SECTION
4 monitored control lines for
"Sector valve"
"Main valve"
"Alarm horn"
"Illuminated warning panel"
5 Monitored detection lines for
"Manual activation"
"Stop or blocking button" (Function selectable)
Signal contact "Loss of extinguishing agent"
Signal contact "Extinguishing blocked"
Signal contact "Extinguishing activated"
LON interface for separate extinguishing B3Q440 control consoles
Enables up to 4 local B3Q440 extinguishing control consoles
Line and equipment are monitored (not short circuit proof)
Individual parameterization via maintenance PC (AlgoWorks)
Downloading of user functions from AlgoWorks via control unit and storage on
E3G080 direct
Maintenance switch for automatic calibration and line read–in function
Integrated emergency operation function
Selectable ground fault monitoring, detected via master module E3X10. (for ap-
plication details –> see chapter 6)
I-Bus address is set with programming switch "S3"
Card format 100 mm x 200 mm
module E3G080 is required for each extinguishing SECTION
a B3Q440 control console is required for each extinguishing SECTION (max. 4
possible)
Application without the B3Q440 control console is possible, but not recom-
mended
the total current per E3G080 (valve, alarm horn, illuminated warning panel etc.
active) may not exceed 4 A
Terminal block X10 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to
connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
Separate extinguishing control console
B3Q440
001260_k_en_--.doc
02.2005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents