Z3I040, Z3I120, Z3I130 Surge protector set (superseded by Z3I041, Z3I121)
15
Z3I040, Z3I120, Z3I130 Surge protector set
Z3I041, Z3I121)
15.1
Overview
15.2
Application example
Z3I040 /120 /130
N
N
UCV
L
L
UCV
L
L
74
Building Technologies
Fire Safety & Security Products
Additional protection against surge voltage peaks in the mains lead (Option)
3 different surge protector sets available
Z3I120: 110 VAC
–
Z3I040: 230 VAC
–
Z3I130: and zero point floating ground (= 380 VAC type)
–
Application
In systems particularly at risk from lightning, such as transformer systems or al-
–
pine transmitting stations etc.
Z3I120 can also be used as a supplementary measure against static discharge
–
on detection lines or data lines
1 surge protector set per switchgear cabinet or per mains lead is enough
–
1
2
Legend:
1
Surge protector cartridge UCV... (2x)
2
Surge protector terminal (2x)
3
Fuse terminal (1x)
4
Ground terminal (2x)
5
Can be mounted on DIN extruded section in the control unit (instead of mains
terminals)
B2F020
E
E
N
N
L
Incorrect
L
DANGER
3
4
5
Z3I040 /120 /130
N
UCV
L
UCV
L
max. 10A
(superseded by
E
N
N
Mains supply
L
Ground connec-
tion via mount-
L
ing flange and
L
DIN extruded
section
001260_k_en_--.doc
02.2005