E3G110 Emergency operation link

40.1
Overview
40.2
Application
40.3
Key data
Building Technologies
Fire Safety & Security Products
Optional unit to E3G080 'Extinguishing' control module (vital function in 'D')
Enables autom. activation of extinguishing upon malfunction of the main CPU
when linked to 2 detectors
Receives "Emergency alarm" via the Mimic display output of the line module be-
longing to the extinguishing SECTION
1..8 line modules can be allocated to 1..4 link channels
E3G110 is independent of control unit software
Allocation made by inserting jumpers in the 'Mini distributor board' in the
E3G110
Link to the line modules E3M060, E3M070, E3M071, E3M080, E3M111,
E3M140 and E3M171
Card format 100 mm x 200 mm
The detectors in the extinguishing SECTION must be assigned to 2 independ-
ent detection lines.
With collective detectors the 2 detection lines can be on the same or different
modules.
Several link channels can be connected in parallel if several line pairs belong to
the extinguishing SECTION.
The flat cables F12A100 (0.4 m) or F12A470 (1.5 m) are used for the connection
between line module E3M... and E3G110.
In order to monitor the presence of the E3G110, the manual activation line
(E3G080) can be 'looped' via the E3G110. However, the E3G110 can also be
connected to the E3G080 as a 'stub' line.
For further details –> see Principle of interlinking, page 166
Inputs
8 (Flat cables ST1 - ST8) designed for Mimic display outputs E3M....
Outputs
4 (Link channels) designed for 'Simulation of manual activation' E3G080
Quiescent current
0 mA
Terminal block X10 (20 terminals)
mounted on module chassis
for connection to control module E3G080 (manual activation)
Card chassis
mounted on module chassis
E3G110 Emergency operation link
001260_k_en_--.doc
165
02.2005