E3X101 Master module (superseded by E3X102/103)
42
Building Technologies
Fire Safety & Security Products
12
Maintenance switch "S4": "Maintenance functions"
"S4-1...10" are set to "off" at the factory
S4 - 1...8
unused
S4 - 9
Switch on / off red LEDs (H2...H7) on E3X101
S4 - 10
Maintenance mode. Blocks all control outputs and activates the corresponding
LED:
Module
E3X101
E3L020
E3G050
E3G060
E3G070
Extinguishing control module E3G080 is not included in the blocking of the S4-
10.
Also blocks the monitoring of the 'Emergency operation circuit fire alarm'.
13
Plug-in terminals "K2": Remote transmission equipment
14
Lithium battery 3 V / 70 mAh: RAM buffering for clock, user data etc.
data storage time: minimum 2 weeks, typical >100 days
maintenance-free
15
Double flat cable header "ST1" (26-pin): I-Bus
16
Key "S10": System start only with battery (without mains voltage)
17
Plug-in terminals "K1": Supply for the "I-Bus" modules
18
LED indicator block "Battery charger"
yellow
green
H501
yellow
H502
yellow
Indicators vary in meaning according to application:
a) Battery operation
LED "Power supply fault
and symmetry moni-
toring
LED "Power on"
LED "Battery fault
b) Battery operation
LED "Power supply fault
without symmetry
monitoring
LED "Power on"
LED "Battery fault
c) Operation with
LED "Power supply fault
external voltage (in-
stead of battery)
LED "Power on"
Control outputs
Q1 ... Q8
I/O1 ... I/O16
K1 ... K8
1........6
Q1....Q7
"Power supply fault"
"Mains operation"
"Battery fault"
unused
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5 V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
Input voltage > 28.5 V
Battery voltage < 23 V
Asymmetry > 1.0 V or fuse F503 blown
Possibly cell short circuit
Open line to battery or fuse F501 / F502 blown
Autom. test to indicate battery presence negative
Autom. battery load test negative
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
Input voltage > 28.5 V
Battery voltage < 23 V
Open line to battery or fuse F501 / F502 blown
Autom. test to indicate battery presence negative
Autom. battery load test negative
Input voltage > 31.0 V –> power unit malfunction
EEPROM check sum error
Input voltage > 28.5 V
LEDs
H2 ... H5
H1 ... H16
H1 ... H8
H1 ... H6
H5... H11
001260_k_en_--.doc
02.2005