E3M060 Line module "MS9i"

18.1
Overview
18.2
Key data
Building Technologies
Fire Safety & Security Products
Line module for addressable detectors MS9i
I-Bus module with line processor and independent emergency operation proces-
sor
Designed for 1 loop line or stub line
Line inputs protected against over voltage
Card format 100 mm x 200 mm
I-Bus address is set at the programming switch "S3"
Addresses
Number of wires
Twisted cable
Line resistance
Line capacitance
Short–circuit proof
T-branch
Quiescent current at 24 V
1) With < 50 elements a higher line resistance is permissible, for details –> see
document 825
Terminal block X20 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
E3M060 Line module "MS9i"
max. 50
2
necessary
...50 Ω (with 50 MS9i elements) 1)
...300 nF
yes (line separator in each MS9i detector or MS9i element)
no
170 mA with 50 detectors
79