Capacitance Switches
Pointek CLS200/CLS300 (Standard)
Operating Instructions 09/2009
SITRANS

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Pointek CLS200

  • Page 1 Capacitance Switches Pointek CLS200/CLS300 (Standard) Operating Instructions 09/2009 SITRANS...
  • Page 2 The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
  • Page 3: Table Of Contents

    Wiring: Pointek CLS200/300 standard ..............20 Relay Output Connection ......................21 Solid-state Switch ........................21 Diode Protection ........................22 Power Connection ........................22 Functionality Test ..........................23 Operation: Pointek CLS200/300 standard model ..........24 User Interface ..........................24 Indicators ............................24 Alarm Output ..........................25 Switch Bank ..........................26 Setup ............................27...
  • Page 4 Detection Range ..........................32 The Pointek CLS200 electrode ....................33 The Pointek CLS300 electrode ....................34 Pointek CLS200 Standard Pressure versus Temperature Curves ........35 CLS200 compact and extended rod versions, threaded ..........35 CLS200 cable version, threaded ....................36 CLS200 sanitary compact and extended rod versions .............36 CLS200 compact and extended rod, ASME welded flange ..........36...
  • Page 5 Fault Signaling ...........................70 Glossary ..........................71 Index ..........................73...
  • Page 7: Safety Notes

    Please follow the installation and operating procedures for a quick, trouble-free Note: installation and to ensure the maximum accuracy and reliability of your Pointek CLS200/ 300. This manual applies to the Pointek CLS200/300 Standard model only. Pointek CLS200/300 is available in two models, standard and digital. For information on the CLS200/300 digital model, please see manual 7ML19985JJ01.
  • Page 8: Application Examples

    Technical Support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone number and fax number go www.siemens.com/automation/partner • Click on the tab Contacts by Product then drill down to find your product group (+Process Automation >...
  • Page 9: Abbreviations And Identifications

    Farads Farad Process Device Manager configuration tool PEEK Polyaryletheretherketone organic polymer Polyphenylene Sulfide polymer PTFE Polytetrafluoroethylene thermoplastic fluoropolymer PVDF Polyvinylidene Fluoride engineered fluoropolymer 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 3...
  • Page 10: Pointek Cls200/300 Standard

    For information on the CLS200/300 Digital, please see manual 7ML19985JJ01. • Pointek CLS200/300 is to be used only in the manner outlined in this instruction manual, otherwise protection provided by the equipment may be impaired.
  • Page 11: Pointek Cls200/300 Applications

    When used with a SensGuard protection cover, the CLS200 sensor is protected from shearing, impact, and abrasion, in tough primary processes. Pointek CLS200/300 Applications Pointek CLS200/300 is designed for level detection and simple pump control in a variety of applications: •...
  • Page 12: Specifications: Standard Model

    Specifications: standard model Siemens Milltronics makes every attempt to ensure the accuracy of these Note: specifications, but reserves the right to change them at any time. Pointek CLS200/300 Power • supply 12 to 250 V AC/DC (0 to 60 Hz) •...
  • Page 13: Mechanical

    • Welded flange: (optional FFKM) ASME: 1” , 1 ½” , 2” , • PPS probe 3” or 4” (optional PVDF) DN 25, 40, 50, 80 or 100 Or 1.4404 material. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 7...
  • Page 14 (R), BSPP (G) or NPT; version 1 ¼” NPT only • Welded flange: ASME: 1” , 1 ½” , 2” , 3” or 4” DN 25, 40, 50, 80 or Page 8 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 15: Environmental

    The use of approved watertight conduit hubs/glands is required for Type 4 / Note: NEMA 4, Type 6 / NEMA 6, IP68 (outdoor applications). Weight Weight varies based on configuration. For example: • compact Pointek CLS200/300, 1 kg (2.20 lb.) approx. 100 mm (4”) insertion length, 3/4” process connection Environmental • location indoor/outdoor •...
  • Page 16: Process

    Process Pointek CLS200 Standard Pressure versus Temperature Curves Please see Note: Pointek CLS300 Standard Pressure versus Temperature Curves on page 35. • relative dielectric constant (εr) 1.5 minimum • CLS200 temperature: - without thermal isolator –40 to 85 °C (–40 to 185 °F) - with thermal isolator –40 to 125 °C (–40 to 257 °F)
  • Page 17 ATEX II 1/2 D T100°C • Marine Lloyds Register of Shipping, Categories ENV1, ENV2 and ENV5 • Overfill Protection WHG (Germany) • Others SIL/IEC61508 Declaration of Conformity [SIL-2(overspill)], Pattern Approval (China) 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 11...
  • Page 18: Installation: Pointek Cls200 Standard

    • Provide a sun shield to protect the transmitter from direct heat radiation. Precautions: • Avoid mounting Pointek CLS200 in locations subject to strong vibrations in the vicinity, whenever possible. Environmental • Do not exceed the permissible ambient temperature limits (see page 9 for details).
  • Page 19: Mounting Restrictions

    Pointek CLS200 typical configuration with extensions: For high or low level alarm: • designed for top mounting. The probe suspends vertically so that it reaches into the process at the desired detection level (high or low detection alarm). High level alarm...
  • Page 20: Cls200 Dimensions

    Sensors must be at least 100 mm (4") apart. Mount diagonally if space is restricted CLS200 Dimensions Appendix E: Dimensions for all versions of the Pointek CLS200 Standard can be found in Dimensions - CLS200 starting on page 47. Page 14 Pointek CLS200/300 Standard –...
  • Page 21: Process Cautions

    Caution: Tensile load must not exceed Caution: Consider material surface Tensile probe or vessel rating (See configuration when installing unit. (max) on page 7.). 50 mm (2") min Caution: Avoid areas where material build up occurs. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 15...
  • Page 22: Installation: Pointek Cls300 Standard

    • mounted through the tank wall at the detection level For low level alarm (level drops below normal process level): • mounted through the tank wall at the detection level Page 16 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 23: Mounting Restrictions

    Multiple Units Side View End View (section) 500 mm (20") min 500 mm (20") min 500 mm (20") min Mount diagonally if space is restricted. Sensors must be 500 mm (20") apart. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 17...
  • Page 24: Process Cautions

    • Consider material surface configuration 500 mm when installing unit. (20") min • Tensile load must not exceed probe or vessel rating. Page 18 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 25: Cls300 Dimensions

    Buildup of material in Active Shield area does not affect switch operation. Note: CLS300 Dimensions Appendix F: Dimensions for all versions of the Pointek CLS300 Standard can be found in Dimensions - CLS300 starting on page 55. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 19...
  • Page 26: Wiring: Pointek Cls200/300 Standard

    Ground the instrument according to local regulations. Tighten the gland to form a good seal. If you wish to carry out a function test, follow the test procedures on page 23. Page 20 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 27: Relay Output Connection

    Solid-state switch to customer's control or instrumentation device. The switch is shown in de-energized/unpowered state. K3 contact ratings: • Maximum Voltage: 30 V DC or peak AC • Maximum Current: 82 mA • Non-polarized 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 21...
  • Page 28: Diode Protection

    V DC 22 to 26 V 46 to 50 V 120 Ω 234 Ω 12 to 250 V AC/DC Connect protective earth wire to terminal provided in housing and marked with Page 22 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 29: Functionality Test

    Grasp the probe with your hand. The yellow sensor status light L1 will glow, indicating switch function. After an appropriate delay the red output status light L3 will glow. This concludes the switch function test. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 23...
  • Page 30: Operation: Pointek Cls200/300 Standard Model

    (relay energized/ (material capacitance greater than setpoint for P2) switch closed) sensor not contacting process material alarm ON Unlit (material capacitance less than setpoint for P2) (relay de-energized/ no power switch open) Page 24 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 31: Alarm Output

    Failsafe The Failsafe function controls the response of Pointek CLS200/300 to a fault so that the Fault Signaling process will be put into a safe mode of operation. (See on page 70 for further details).
  • Page 32: Switch Bank

    High alarm/ overfill protection S2-ON disables delay of alarm activation (alarm ON) S1-ON disables delay of alarm activation (alarm ON) Low alarm/dry run protection S2-ON disables delay of alarm de-activation (alarm OFF) Page 26 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 33: Setup

    Initial setup can be carried out prior to mounting into the process, but it is extremely important to calibrate the unit and adjust the sensitivity on the product itself. For a simple application, set Pointek CLS200/300 to Low alarm/no delays: •...
  • Page 34: Start Up

    Start Up After Pointek CLS200/300 is properly mounted and the switch bank is set up, apply power to the unit. The green LED (L3) glows, indicating the unit is powered and operational. Setpoint Adjustment delay: alarm activation delay: alarm deactivation...
  • Page 35 Delay alarm output If you want to slow the Pointek CLS200/300 response, to compensate for turbulence or false readings, set a delay interval using potentiometer P1, and set S1 and/or S2 to OFF, to enable the delay for either alarm activation, alarm de-activation, or both.
  • Page 36 S2-ON disables delay of alarm de-activation (alarm OFF) To test the delay function, follow the test procedure on page 23. Operation After completing the setup, replace the lid and secure the lid clip. Pointek CLS200/300 standard model is now ready to operate. Page 30 Pointek CLS200/300 Standard –...
  • Page 37: Troubleshooting: Pointek Cls200/300 Standard Model

    Check that relay changes switch on when sensor is covered. state when S3 is toggled ON sensor is covered. and OFF. L1 (yellow) flashes when material level approaches the alarm setpoint. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 31...
  • Page 38: Appendix A: Technical References

    High Frequency Oscillator The Pointek CLS200/300 probe is equipped with a high frequency oscillator which responds to the capacitance. The inverse of frequency is proportional to the capacitance.
  • Page 39: The Pointek Cls200 Electrode

    The Pointek CLS200 electrode The Pointek CLS200 electrode is the primary sensor of the system. It supplies the electrical capacitance value. The reference is the environment at the time of setup.
  • Page 40: The Pointek Cls300 Electrode

    Page 34 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 41: Pointek Cls200 Standard Pressure Versus Temperature Curves

    The powder-coated aluminum enclosure provides reliable operation in environments with dust, moisture, and high-frequency interference. Pointek CLS200 Standard Pressure versus Temperature Curves CLS200 compact and extended rod versions, threaded P = permitted operating pressure T = permitted operating temperature atmospheric 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 35...
  • Page 42: Cls200 Cable Version, Threaded

    CLS200 compact and extended rod, ASME welded flange P = permitted operating pressure T = permitted operating temperature atmospheric 1) The curve denote the minimum allowable flange class for the shaded area below. Page 36 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 43: Cls200 Cable, Asme Welded Flange

    1) The curve denote the minimum allowable flange class for the shaded area below. CLS200 cable, EN welded flange P = permitted operating pressure T = permitted operating temperature atmospheric 1) The curve denote the minimum allowable flange class for the shaded area below. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 37...
  • Page 44: Pointek Cls300 Standard Pressure Versus Temperature Curves

    (435 psi) at 75 °C atmospheric P = permitted operating pressure T = permitted operating temperature CLS300 high temperature rod version, threaded P = permitted operating pressure T = permitted operating temperature atmospheric Page 38 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 45: Cls300 Standard, Extended Rod And Cable Versions, Asme Welded Flange

    CLS300 high temperature rod version, ASME welded flange P = permitted operating pressure T = permitted operating temperature atmospheric 1) The curve denote the minimum allowable flange class for the shaded area below. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 39...
  • Page 46: Cls300 Standard, Extended Rod And Cable Versions, En Welded Flange

    CLS300 high temperature rod version, EN welded flange P = permitted operating pressure T = permitted operating temperature atmospheric 1) The curve denote the minimum allowable flange class for the shaded area below. Page 40 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 47: Appendix B: Maintenance And Repairs

    Please note the following: • The user is responsible for all changes and repairs made to the device. • All new components must be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
  • Page 48: Appendix C: Product Nameplates

    Appendix C: Product Nameplates Information in boxes 1 through 7 changes based on customer order. Note: Pointek CLS200 Page 42 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 49: Pointek Cls300

    Pointek CLS300 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 43...
  • Page 50: Appendix D: Hazardous Area Installation

    10 for the specific configuration you are about to use or install. • In potentially explosive atmospheres: - open the enclosure only when Pointek CLS200/300 is not energized. - if a transmitter is to be used as category 1/2 equipment, please...
  • Page 51 Suitable precautions: e.g. establishing from the material's data sheet that it is resistant to specific chemicals. Please see www.siemens.com/pointek for the latest approval certificates. Note: Operating the CLS200 Flameproof / Explosion Proof configuration in hazardous areas ATEX Maximum permissible ambient temperature range in potentially explosive...
  • Page 52 Maximum permissible process temperature range in potentially explosive atmospheres: –40 °C to maximum +200 °C (–40 ºF to maximum+ 392 ºF ) –40 °C to maximum +400 °C (–40 ºF to maximum +752 ºF ): high temperature version Page 46 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 53: Appendix E: Dimensions - Cls200

    M20: 135 mm (5.32") ½" NPT: 150 mm (5.91") 150 mm (5.91") 272 mm (10.83") thermal isolator Compact Version, threaded electronics/ enclosure 22 mm 120 mm (0.87") (4.7") PPS or optional PVDF probe 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 47...
  • Page 54 Min. insertion length = 200 mm (7.87") Max. insertion length = 5500 mm (216") Sanitary Compact Version 316L stainless steel sanitary process connection 98 mm (3.80") PPS or optional PVDF probe Page 48 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 55 24 mm PPS or optional Ø PVDF probe (0.95") 98 mm (3.80") Y01 (insertion length) Min. insertion length = 110 mm (4.3") Max. insertion length = 5500 mm (216") 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 49...
  • Page 56 (insertion length) min. 215 mm (8.46") 20 mm (0.79") Ø 84 mm PPS or optional (3.3") PVDF probe Min. insertion length = 350 mm (13.82") Max. insertion length = 5500 mm (216") Page 50 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 57 316L stainless steel sensor weight 20 mm (0.79") Ø 84 mm (3.3") PPS or optional PVDF probe Min. insertion length = 500 mm (19.69") Max. insertion length = 35000 mm (1378") 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 51...
  • Page 58 165 mm (6.50") 290 mm (11.42") thermal isolator Flange Facing Table Flange Facing (raised face) Flange Class Facing thickness ASME150/300 2 mm (0.08") ASME600/900 7 mm (0.28") PN16/40 2 mm (0.08") Page 52 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 59 316L stainless steel PPS or optional 20 mm Ø extension PVDF probe (0.79") 84 mm (3.3") Y01 (insertion length) Min. insertion length = 200 mm (7.87") Max. insertion length = 5500 mm (216") 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 53...
  • Page 60 316L stainless steel sensor weight 20 mm (0.79") Ø 84 mm (3.3") PPS or optional PVDF probe Min. insertion length = 500 mm (19.69") Max. insertion length = 30000 mm (1181") Page 54 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 61: Appendix F: Dimensions - Cls300

    Appendix F: Dimensions - CLS300 Threaded Processs Connection 2 cable entries ½" NPT or M20x1.5 M20: 135 mm (5.32") ½" NPT: 150 mm (5.91") 165 mm 290 mm (6.50") (11.42") thermal isolator 7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUAL Page 55...
  • Page 62 = 1000 mm (39.37") probe measuring length Extended Active Shield (Y02): standard length 125 mm (4.92") Optional Active Shield lengths: 250 mm (9.84") or 400 mm (15.75" 19 mm (0.75") Ø Page 56 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 63: High Temperature Rod Version, Threaded

    High Temperature Rod Version, threaded Thermal isolator Extended Active Shield (Y02): standard length 125 mm (4.92") Optional Active Shield lengths: Ceramic insulator(s) 250 mm (9.84") or 400 mm (15.75") Y01 (insertion length) min. = 350 mm (14") max. = 1000 mm (39") measuring length probe...
  • Page 64: Non-Insulated Cable Version, Threaded

    Ø Extended Active Shield (Y02): standard length 125 mm (4.92") Optional Active Shield lengths: 250 mm (9.84") 250 mm (9.84") or 400 mm (15.75") stainless steel weight 32 mm (1.26") Ø Page 58 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 65: Insulated Cable Version, Threaded

    Insulated Cable Version, threaded Y01 (insertion length) min. = 1000 mm (40") max. = 25000 mm (984") measuring insulated cable length 10 mm (0.35") Ø 250 mm stainless steel weight (9.84") Extended Active Shield (Y02): 32 mm (1.26") Ø standard length 125 mm (4.92") Optional Active Shield lengths: 250 mm (9.84") or 400 mm (15.75") 7ML19985JH01...
  • Page 66: Cls300 - Flanged Process Connections

    290 mm 165 mm (11.42") (6.50") thermal isolator Flange Facing Table Flange Facing (raised face) Flange Class Facing thickness ASME150/300 2 mm (0.08") ASME600/900 7 mm (0.28") PN16/40 2 mm (0.08") Page 60 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 67: Rod Version, Welded Flange

    Rod Version, welded flange lid clip electronics/ enclosure Active Shield Y01 (insertion length) min. = 250 mm (9.8") max. = 1000 mm (39.37") probe measuring length 19 mm (0.75") Ø 7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUAL Page 61...
  • Page 68: High Temperature Rod Version, Welded Flange

    Optional Active Shield lengths: 230 mm (9.06") or 380 mm (14.96") Y01 (insertion length) min. = 250 mm (9.8") max. = 1000 mm (39.37") measuring length probe 19 mm (0.75") Ø Page 62 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 69: Non-Insulated Cable Version, Welded Flange

    Non-insulated Cable Version, welded flange Extended Active Shield (Y02): standard length 105 mm (4.13") Optional Active Shield lengths: 230 mm (9.06") or 380 mm (14.96") Insertion length does not include any raised face/gasket face Flange Facing dimension (see the Table on page 60).
  • Page 70: Insulated Cable Version, Welded Flange

    (9.84") 230 mm (9.06") or 380 mm (14.96") weight Insertion length does not include any raised face/gasket face dimension (see Flange Facing Table on page 60). 32 mm (1.26") Ø Page 64 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 71: Appendix G: Shortening The Cable

    Steps Unscrew the cable gland compression nut to relieve the sealing cone and release the cable. cable gland compression nut probe sleeve probe, lower assembly 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 65...
  • Page 72 Calculate the excess cable, then add back an allowance of 75 mm (3") for making the connections: For example, 1000 mm = excess less 75 mm = allowance for connections 925 mm = excess cable to be removed Cut off the excess cable. Page 66 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 73 16. Screw the lower probe assembly clockwise into the probe sleeve, and tighten it with a 17 mm (0.67") wrench. 17. Check that the instrument is operating correctly, using the test procedure on page 23. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 67...
  • Page 74: Pointek Cls300 Standard, Cable Version

    Make sure that no cable strands are pushed out of their position in the cable and that the cable is fully inserted. Re-fasten the weight by tightening the three set screws. cable weight Page 68 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 75: Appendix H: Application For Pointek Cls200/300 Standard

    The setting is selected by turning dip switch 3 on or off. Or, if the trip point is set to detect the approaching level, when that trip point is reached. Page 69 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 76 25, and make the appropriate connections to suit your application. Failsafe High is used in applications where Pointek CLS200/300 is set to turn off a pump when the level becomes too high (probe covered, or level too close to probe). When Failsafe High is selected, the device will respond to a failure (regardless of the true level) as if it were a high level alarm (alarm ON/solid-state switch open).
  • Page 77 Many conductive liquids/electrolytes exhibit dielectric properties; the relative dielectric constant of water is 80. 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 71...
  • Page 78 Notes Page 72 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 79 (analog) 28 requirements 44 setup (analog) 27 high frequency oscillator 32 shortening the cable 65 High Temperature Version 57 solid-state switch Dimensions 57 contact status (analog) 21 7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 73...
  • Page 80 (analog) 28 tension block 66 test settings (analog) 27 troubleshooting (analog) 31 wiring (analog) 20 Page 74 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01...
  • Page 81 Siemens Milltronics Process Instruments Inc. Subject to change without prior notice Industry Automation (IA) 7ML19985JH01 Rev. 1.0 1954 Technology Drive P.O. Box 4225 *7ml19985JH01* © Siemens Milltronics Process Instruments Inc. 2009 Peterborough, ON Canada K9J 7B1 Printed in Canada email: techpubs.smpi@siemens.com www.siemens.com/processautomation...