Siemens Cerberus CS1140 Manual page 52

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3X102/103 Master module (supersedes E3X101)
52
Building Technologies
Fire Safety & Security Products
Legend:
1
Jumper 'X61': Remote alarm" make / break contact
Jumper on 2-3 = make contact (factory setting)
1-2 = break contact
2
Jumper "X60": Ground fault monitoring 'control unit'
'out' = inactive (factory setting)
'in'
= active
Details application see chapter 6
3
SRAM
E3X102: 2x512Kx8Bit:
E3X103: 4x512Kx8Bit
user data and standard text
4
Flash-ROM 2MBx8Bit: Software factory programmed:
E3X102 program file CCX00xxx
E3X103 program file CCY00xxx
5
Programmable switch 'S5': "Service and horn functions"
'S5-1...4' are set to "off" at the factory
S5-1
on
durability reset (maintenance function for testing purpose only)
off
normal operation
S5-2*
off
flash programming disabled
on
flash programming enabled (this function for production and service engineer only)
S5-3
off
control line alarm horns on continuous tone
on
control line alarm horns intermittent 1 s/ 1 s (during emergency operation the alarm
horns are switched to continuous tone)
S5-4
on
unused
*) Carry out a CPU reset (switch 'S1') after each switch over of 'S5-2'.
6
Resistances to adapt the C-Bus impedance:
Position
R178 / 179
R196 / 197 / 198 / 199
Impedance adaptation only required if C-bus line is > 100 m.
For calculation of adaptation resistors for other impedance values than 110 Ω or
50 Ω –> see document 1594
7
Connector "ST2": RS232 (2x HCMOS level), connection to E3I020
– is also used as interface to the maintenance PC
8
LED indicator block "CPU functions"
yellow
green
H1
red
red
H2
red
red
H3
red
red
H4
red
red
H5
red
red
H6
red
red
H7
1) fast flashing: no data loaded yet; slow flashing: data loaded
9
Jumper "X30": Ground fault monitoring 'C-Bus'
'J1'
= not monitored (factory setting)
Impedance value 110 Ω, e.g. for
G51 0.6 Ø
402 Ω
inserted at factory
110 Ω
"Emergency operation"
"Normal operation" 1)
Output Q1 active
Output Q2 active
Output Q3 active
Output Q4 active
Output Q5 active
Output Q6 active
Output Q7 active
Output Q8 active
Horn 1 active
Horn 2 active
Remote transmission "Alarm" active
Remote transmission "Fault" active
Impedance value 50 Ω,
e.g. for MICC
182 Ω
49.9 Ω
001260_k_en_--.doc
02.2005