Siemens Cerberus CS1140 Manual page 142

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3G060 Control module "monitored" (Part No 460514)
34.5
Connections (Part No 460514)
E3G060
unused
Monitored
LED
control line 1
Monitored
LED
control line 2
Monitored
LED
control line 3
Monitored
LED
control line 4
LED
Monitored
Module chassis ground
control line 5
Monitored
LED
control line 6
unused
Plug-in terminals
Supply for
I-Bus modules
F19
Double flat cable header
Data communication
I-Bus modules
142
Building Technologies
Fire Safety & Security Products
X1
Terminal block
1
-
2
F2
H1
24V
F1
+
3
1)
F4
-
4
H2
F3
+
5
-
6
F6
H3
+
7
F5
-
8
F8
H4
F7
+
9
-
10
H5
F10
11
(connect to chassis ground)
+
12
F9
-
13
F12
H6
24V
F11
+
14
15
16
17
18
19
20
K1
-
1
blue
GND
2
-
blue
5V
+
3
green
24V
+
4
red
ST1
1) The indicated polarity at the terminals 2...14 applies to the active state
max. 2A
4.75kΩ
4.75kΩ
max. 2A
from previous I-Bus modules
to other I-Bus modules
from previous I-Bus modules
to other I-Bus modules
001260_k_en_--.doc
02.2005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents