37.3
Key data for E3G080 until index 'AB'
Type of line
Control lines
'Sector valve'
'Main valve'
Control lines
'Alarm horn'
'Illuminated warning panel'
Detection lines
'Manual activation'
'Stop/blocking button'
Detection lines
'Loss of extinguishing agent'
'Extinguishing blocked'
Detection line
'Extinguishing activated'
Control console for B3Q440
serial interface
* reversed polarity in 'active' status
** with mains operating 29 V
37.4
Key data for E3G080 from index ≥ 'AB' (Type FM)
Type of line
Control lines
'Sector valve'
'Main valve'
Control lines
'Alarm horn'
'Illuminated warning panel'
Detection lines
'Manual activation'
'Stop/blocking button'
Detection lines
'Loss of extinguishing agent'
'Extinguishing blocked'
Detection line
'Extinguishing activated'
Control console for B3Q440
serial interface
* reversed polarity in 'active' status
** with mains operating 29 V
37.5
Control lines
37.5.1 Control line "Sector valve"
Building Technologies
Fire Safety & Security Products
Termi-
Line voltage
nals
'quiescent'
X10–..
(line termination with 4k75)
1/2
without R60/61 –> 80..800 mV
2/3
without R60/61 –> 0.3...1.6 V
4/5
2.3 V ± 10 %
6/7
8/9
14.25 V ± 10 %
9/10
12/13
2.3 V ± 10 %
14/15
16/17
17 V **
18/19
Termi-
Line voltage
nals
'quiescent'
X10–..
(line termination with 4k75)
1/2
ohne R60/61 –> 80..800 mV
2/3
mit R60/61 –> 0,3...1,6 V
4/5
2,3 V ± 10 %
6/7
8/9
14,25 V ± 10 %
9/10
12/13
2,3 V ± 10 %
14/15
16/17
17 V **
18/19
To activate the extinguishing valve up to a max. 2 A total current
–
active upon 'extinguishing released' upon expiry of the delay period until ex-
–
piry of the permissible operating time or until reset
monitored for open line / short circuit
–
Upon open line / short circuit, in addition to a fault signal, an "autom. + manual
–
activation blocked" signal is given
valve coil as line termination element
–
automatic calibration by means of maintenance key "S4" (–> see page 156)
–
Parameters can be set via AlgoWorks –> see document 005109
E3G080 Control module "Extinguishing"
Monitoring
Line
current
voltage
'open line'
≥ 880 mV
5 mA
≥ 1.75 V
≥ 3.5 V
0.5 mA
3 mA
≥ 15 V
0.5 mA
≥ 3.5 V
≥ 22 V **
resistor 3k3
Voltage cannot be measured with a voltmeter
Monitoring
current
voltage
'open line'
≥ 880 mV
5 mA
≥ 1,75 V
0,5 mA
≥ 3,5 V
≥ 25 V
4,7 mA
≥ 3,5 V
0,5 mA
resistor
2k25
≥ 22 V **
Spannung nicht messbar mit Voltmeter
Line
voltage 'short
circuit'
≤ 100 mV
≤ 200 mV
≤ 350 mV
24...30 V *
≤ 1.7 V
≤ 350 mV
400 mV..1.3 V
≤ 2.7 V **
3...14 V **
Line
Line
voltage 'short
circuit'
≤ 100 mV
≤ 200 mV
≤ 350 mV
≤ 2,6 V
≤ 350 mV
400 mV..1,3 V
≤ 2,7 V **
001260_k_en_--.doc
Line
voltage
'active'
Section
24...30 V
2...10 V
Line
voltage
'active'
Section
24...30 V
24...30 V *
3...12 V
3...14 V **
151