Important Components - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

K3R071 Mimic Display board (superseded by K3R072)
49.6

Important components

210
Building Technologies
Fire Safety & Security Products
1
ST2
2
F1
3
K1
4
X56
5
X48
Legend:
1
48 plug-in connectors, 2-pin: 2-wire cable (cable set Z3I520 = 12 cables) to
LEDs in Mimic display
2
Connector "ST1" / "ST2": Connection of data bus via flat cable
3
Fuse 'F1'
0.4 A/T:
4
Programming switch "S1": Equipment address setting
No.
Test procedure:
In this setting all outputs are activated alternating between even
0
and uneven numbers.
1
Equipment address 1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
"S1-1...4" are set to "off" at the factory
5
Plug-in connector "X56": Output for LED 'Operation'
6
Plug-in connector "X49": Output for 'Buzzer'
7
Plug-in connector "X50": Input for key 'Lamp test'
8
Plug-in connector "X55": Input for key 'Switch-off buzzer'
9
Plug-in terminals "K1", 4 pin: Power supply 9...45V DC
10
Plug-in terminals "K2", 6 pin: Connection of data bus instead of flat cable
11
Resistor array (assembled ex work / must be assembled only for one device)
X1
K2
11
ST1
S1
ON
1
4
1
9
8
7
X55
6
X50
X49
Supply input 9...45 VDC
Function
6
1
10
Programming switch S1
S1-1
S1-2
off
off
on
off
off
on
on
on
off
off
on
off
off
on
on
on
off
off
001260_k_en_--.doc
S1-3
S1-4
off
off
off
off
off
off
off
off
on
off
on
off
on
off
on
off
off
on
02.2005

Hide quick links: