E3I040 I-Bus/LON module

28
E3I040 I-Bus/LON module
28.1
Overview
28.2
Application
28.3
Key data
Number of devices per line
LON-Bus:
number of wires
cable type
max. cable length
LON-Bus: connection
Typical current consumption (24 V)
Rating supply output (pin 9/10)
114
Building Technologies
Fire Safety & Security Products
Converter I-Bus to LON-Bus
Up to 32 LON-Bus devices connectable
With 24 V supply output
Selectable ground fault monitoring, detected via master module E3X10. (for ap-
plication details see chapter 6)
Board format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
Only one module per station possible
Required for all LON applications within CS1140, such as:
LON-I/O p.c.b. K3I110
LON/Mimic Display converter K3I050 with Mimic display drivers K3R071/072 (or
panels B3R051)
Floor panels B3Q580
Fire Brigade Terminals B3Q590/595
Terminal block X2 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
...32
2
twisted (10 twists per m)
standard cable twisted 0.8mm Ø unshielded as 'stub line' ...1000m
same but as 'free topology' 1)
using MICC-cable
using MICC-cable as 'free topology' 1)
using special cable Belden 85102 or 8471
twisted cable necessary
15 mA without load on output (pin 9/10)
max. 860 mA / 20....29.6 V
1) Free topology see chapter 28.4.2
.....500m
.....700m
.....300m
...2700m
001260_k_en_--.doc