E3I040 I-Bus/LON module
28
E3I040 I-Bus/LON module
28.1
Overview
28.2
Application
28.3
Key data
Number of devices per line
LON-Bus:
number of wires
cable type
max. cable length
LON-Bus: connection
Typical current consumption (24 V)
Rating supply output (pin 9/10)
114
Building Technologies
Fire Safety & Security Products
Converter I-Bus to LON-Bus
Up to 32 LON-Bus devices connectable
With 24 V supply output
Selectable ground fault monitoring, detected via master module E3X10. (for ap-
plication details see chapter 6)
Board format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
Only one module per station possible
Required for all LON applications within CS1140, such as:
LON-I/O p.c.b. K3I110
–
LON/Mimic Display converter K3I050 with Mimic display drivers K3R071/072 (or
–
panels B3R051)
Floor panels B3Q580
–
Fire Brigade Terminals B3Q590/595
–
Terminal block X2 (20 terminals)
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
for direct connection of the periphery
–
Card chassis
–
mounted on module chassis
...32
2
twisted (10 twists per m)
standard cable twisted 0.8mm Ø unshielded as 'stub line' ...1000m
–
same but as 'free topology' 1)
–
–
using MICC-cable
using MICC-cable as 'free topology' 1)
–
using special cable Belden 85102 or 8471
–
twisted cable necessary
15 mA without load on output (pin 9/10)
max. 860 mA / 20....29.6 V
1) Free topology see chapter 28.4.2
.....500m
.....700m
.....300m
...2700m
001260_k_en_--.doc
02.2005