37.9

Important components

Building Technologies
Fire Safety & Security Products
1
2
3
4
ASIC
5
I-BUS
ST1
6
S1
ON
S2
H1
ON
H2
H3
7
H4
S4
1
K1
4
Legend:
1
Fuses: "F11, F13, F14, F16"
minated warning panel (Fuses with high breaking capacity, sand-filled)
2
Resistors "R60/61": Choice of internal resistor sector for the main/sector valve
Two areas can be selected for the monitoring of the valves by inserting or remov-
ing resistors. R60 (71k5) is for the sector valve and R61 (71k5) for the main valve.
R60/61 are inserted at the factory.
Valve coil 16...160 Ω
Valve coil 161...320 Ω
3
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Nr.
0
Module out of commission (unused)
1
I-Bus user number 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
E3G080 Control module "Extinguishing"
R61
R60
1
ON
µP
S3
X2
H5
S5
F7
11
10
9
8
2 A/T
Main / sector valve / alarm horn / illu-
= R60/61 removed
= R60/61 inserted
S3-1
off
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
F11
F13
F14
F16
R151
14
13
12
Programming switch S3
S3-2
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
001260_k_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
155