Connections - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3M120 Line module "CBA8000/TS9000"
25.5

Connections

E3M120
Line 1
CBA8000/TS9000 detectors
Loop line
Line 2
CBA8000/TS9000 detectors
Loop line
Line 3
CBA8000/TS9000 detectors
Loop line
Module chassis ground
Line 4
CBA8000/TS9000 detectors
Loop line
unused
Plug-in terminals K1
Supply for
I-Bus modules
Double flat cable header
Data communication
I-Bus modules
106
Building Technologies
Fire Safety & Security Products
Terminal block
J4
+
1
Start
-
2
+
3
Feedback
-
4
+
5
Start
-
6
+
7
Feedback
-
8
+
9
Start
-
10
11
+
12
Feedback
-
13
+
14
Start
-
15
+
16
Feedback
-
17
18
19
20
[J6]
-
1
[4]
blue
GND
-
2
blue
[3]
5V
+
3
[2]
green
24V
+
4
[1]
red
ST1
[J1]
from EP7F, wire the unused lines as loop line
(connect to chassis ground)
from previous I-Bus modules
to other I-Bus modules
from previous I-Bus modules
to other I-Bus modules
CBA8000/TS9000 detectors
Max. 119 addresses
001260_k_en_--.doc