E3G080 Control module "Extinguishing"
37.5.2 Control line "Main valve"
37.5.3 Control line "Alarm horn"
37.5.4 Control line "illuminated warning panel"
37.6
Detection lines
37.6.1 Detection lines "Manual activation"
152
Building Technologies
Fire Safety & Security Products
To activate the pneumatic circuit up to max. 2A total current
–
Active upon 'Extinguishing command' or 'Blocking input active' (terminal 20)
–
until expiry of permissible operating time or until reset
Monitored for open line / short circuit
–
Upon open line / short circuit, in addition to a fault signal, an "autom. + manual
–
activation blocked" signal is given
valve coil as line termination element
–
automatic calibration by means of maintenance key "S4" (–> see page 156)
–
Also operational with 'Emergency operation E3G080'
–
Parameters can be set via AlgoWorks –> see document 005109
To activate electronic alarm horns up to a max. of 2 A total current
–
Start of 'Active status' selectable
–
Monitored for open line / short circuit according to the principle of reversed polar-
–
ity
Function change of alarm tone mode:
–
Until EP5: possible by combining with 'Illuminated warning panel' output (Con-
nection –> see page 158)
≥ EP7F: Programmable via AlgoWorks (Connection –> see page 158)
Line termination with resistor 4k75
–
steady or pulsating is programmable
–
Parameters can be set via AlgoWorks –> see document 005109
To activate illuminated warning panels up to a max. of 2A total current
–
immediately active upon 'Extinguishing command' (inevitable as long as sec-
–
tor valve is active)
monitored for open line / short circuit according to the principle of reversed polar-
–
ity
Line termination with resistor 4k75
–
Parameters can be set via AlgoWorks –> see document 005109
for the initialization of the manual activation of extinguishing (independent of the
–
control unit)
generates 'Extinguishing command' (even if the control unit malfunctions)
–
designed for manual call points, collective (mandatory Z-diode 5.6 V)
–
function 'AI pulse generator'
–
function 'break glass'
–
monitored for open line / short circuit
–
Max. 150 Ω line resistance
–
line termination with resistor 4k75
–
001260_k_en_--.doc
02.2005