Siemens Cerberus CS1140 Manual page 130

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3L020 Control module "I/O"
130
Building Technologies
Fire Safety & Security Products
Legend:
1
Fuses: "F18" 1.25 A/F (monitored) Fuse with high breaking capacity (sand-
filled)
2
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Nr.
0
Module out of commission (unused)
1
I-Bus user number 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
3
Flat cable header "ST1" (26-pin): I-Bus
4
Maintenance switch "S2": Test LEDs H1...H16 Switch on / off. To switch on
maintenance LEDs for test purposes. In addition to driver output, enables the
corresponding LED (H1...H16) to be activated. S2-on = LED (H1... H16)
lights if output is activated.
5
Plug-in terminals "K1": Supply to the "I-Bus" modules
6
Fuse: "F19" 1.6 A/F Module supply (SMD fuse can only be changed at fac-
tory)
7
Fuse: "F1" 0.5 A/T (monitored) Fuse with high breaking capacity (sand-filled)
8
Fuses: "F2...F17"
(can only be changed at factory)
9
Test LEDs "H1...H16" at rear. Allocation of LED see chapter 31.4
S3-1
S3-2
off
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
1 A/F
inputs/outputs 1....16 (not monitored) SMD fuses
Programming switch S3
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
001260_k_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
02.2005