Siemens Cerberus CS1140 Manual page 125

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Building Technologies
Fire Safety & Security Products
3
EPROM plug-in spaces EVEN / ODD: Software
4
RAM plug-in spaces (static RAM)
CK1142:
8 pcs. 256Kx8Bit / Pos. D11... D18 or
4 pcs. 512Kx8Bit / Pos. D11, D12, D15, D16 (ex works)
CK1143:
8 pcs. 512Kx8Bit / Pos. D11... D18
5
Connector (96-pin) "ST10": for interface extension
6
Connector "ST2" (14-pin): "Asynchronous" interface (TTL) to K1D012,
K1D081, K1D121 or K1H021 and AlgoWorks service port
7
Key "S4": Reset
8
Programming switch "S3": "Station address" setting
To set the station address and whether with or without autonomous power supply
Function
≤ EP5:
Station address 16
≥ EP7F:
unused (via SW)
used
E3C011
unused
9
Double flat cable header "ST1" (26-pin):I-Bus from E3C011 (if used)
10
3-pin female connector with 2-pin jumper
11
4-pin female connector
12
Plug-in terminals "K1": Supply line from E3C011 (if used)
13
Plug-in terminals "K2"
14
Lithium battery 3 V / 70 mAh: RAM buffering and clock supply
– Data safeguarded: minimum 2 weeks, typical >100 days
– maintenance free
15
Resistors to modify the C-Bus impedance:
Position
R180 / 183
R173 / 174 / 177 / 178
Impedance adaptation only required if C-Bus line is > 100m. For other impedance
values than 110 Ω or 50 Ω –> see document 1594.
16
Programming of "X1":
Use of E3H020
"CK" + supply from control unit (Input) (X1-17.. 20)
"CK" + autonomous supply (Output) (X1-17.. 20)
17
Programming switch "S5": Interfaces RS232-1 and RS232-2, choice of path
via header "ST2" (external modem) or via terminal block "X2" (internal mo-
dem).
Interface
RS232-1
internal modem via terminal block "X2"
external modem via header "ST2"
RS232-2
internal modem via terminal block "X2"
(Service port)
external modem via header "ST2"
Set to "off" at factory
Programming switch S3
1
2
3
4
off
off
off
off
off
off
off
off
Impedance value 110Ω,
e.g. for G51 0.6mm Ø
402 Ω
110 Ω
Application
E3H020 C-Bus Gateway
5
6
7
8
on
off
on
off
Impedance value 50Ω,
e.g. for MICC
182 Ω
49.9 Ω
0 Ω-resistors
X15 + X16 + X17 + X18
Y15 + Y16 + Y17 + Y18
Programming switch S5
1
off
on
001260_k_en_--.doc