Siemens Cerberus CS1140 Manual page 245

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

56.6
Printer control K3L080
Building Technologies
Fire Safety & Security Products
7
Paper monitoring contact –> Paper end
8
Connection TTL port for modem card (FSK/PSK) (14-wire, 1m) for details –>
see page 242
9
Printer control card K3L080 for details –> see chapter 56.6
Blocking of motor
When the motor is blocked the control unit signals the fault 'Motor blocked'
(according to the type of control unit).
(pre-assembled)
Included with the B2Q191
Mounted in printer card locating frame
Contains the software for printer control
Card format 100 mm x 185 mm
1, 2
3
4
open
X11
5
A2
A1
S2
X12
X13
X14
6
A3
K3
1
7
5
8
Legend:
1
Programming switch «S1»: Choice –> baud rate, communication parameters
and character set
Set 'Printer type 1' in AlgoWorks
Default value printer communication parameter AlgoWorks:
8 data bits / no parity / 1 stop bit
baud rate 9600
If the paper monitoring contact is activated, the control unit indi-
cates a fault 'Paper end'. The printer can then still print out
approx. 200 lines. Thereafter the printing process is discontinued.
When a new paper roll is inserted (paper contact inactive) and the
'Acknowledge' key is pressed, the fault signal is cancelled.
MCU
1
8
F1
S1
H1
10
H2
9
B2Q191 Logging printer
14
D1
13
6
K1
1
K2
2
1
12
11
001260_k_en_--.doc
245
02.2005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents