Connections - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

K3I110 LON I/O p.c.b.
53.7

Connections

K3I110
Plug-in terminals X56
programmable
control output 1
LED 1
programmable
control output 2
LED 2
Plug-in terminals X57
programmable
control output 3
LED 3
programmable
control output 4
LED 4
Plug-in terminals X63
programmable
control output 15
LED 15
programmable
control output 16
LED 16
Plug-in terminals X31
programmable monitored
control input 1
programmable monitored
control input 2
Plug-in terminals X32
programmable monitored
control input 3
programmable monitored
control input 4
Plug-in terminals X37
programmable monitored
control input 13
programmable monitored
control input 14
Plug-in terminals X38
programmable monitored
control input 15
programmable monitored
control input 16
Plug-in terminals K1
not used
Supply 9...45VDC
LON-Bus
R1
230
Building Technologies
Fire Safety & Security Products
1
R1
2
3
R2
4
1
R3
2
3
R4
4
1
R15
2
3
R16
4
*
1
2
3
4
*
1
2
3
4
*
1
2
3
4
*
1
2
3
4
from E3I040 or from previous LON device
1
2
0V
F1
+
3
4
Earth
5
6
to other LON device
* Set the protective circuit according to the tool settings (Default no supervision)
max. 30V / 1A
max. 30V / 1A
A
4k75
B
4k75
1k87
C
4k75
1k87
D
4k75
24V supply
Connection of external contact
Contact
Monitored on
Application
short circuit
NO
NC
A
X
B
X
C
X
D
X
001260_k_en_--.doc
X
X
02.2005