K3G060 Relay Card - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

51

K3G060 Relay card

51.1
Overview
51.2
Key data
51.3
Wiring principle
Relay outputs
1
K2
K3G060
K1
ST1
24V
Data bus relay activation
Building Technologies
Fire Safety & Security Products
Option to Mimic Display board K3R072
2 K3G060 can be connected to each K3R072
Card not monitored
24 volt-free relay-make contacts
Contacts not monitored
Contacts can be individually connected via jumper to externally supplied V+ or
V– potential
Operating voltage
Quiescent current at
all relays de-energized
Max. current
all relays energized
Relay
Contact load
24 Relay outputs
external potential
Data bus
(V+/V–)
ST1 or K2
Datenbus
24
ST1
K3R072
ST11
0,25m
Data bus
9...45 VDC
24 V
6 mA
45 V
6 mA
9 V
7 mA
24 V
90 mA
45 V
50 mA
9 V
270 mA
24 x 1 NO contact
30 VDC
1 A
/
Housing supplied by customer
external potential
(V+/V–)
K2
K1
ST12
0,25m
Data bus
Data bus relay activation
K3G060 Relay card
24 Relay outputs
Relay outputs
1
24
K2
K3G060
ST1
K1
001260_k_en_--.doc
217
02.2005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents