19.3
Special functions
Building Technologies
Fire Safety & Security Products
Emergency operation
Alarm evaluation upon "Emergency operation" via Emergency operation proc-
–
essor and "Emergency operation" in the detector
Upon emergency alarm, control console B3Q... gives a "combined alarm" with
–
flashing response indicator at the detector
Upon line short circuit and failure of the line processor there is no "Emergency
–
alarm"
Mimic display output (connectors ST10) only active with emergency alarm
–
Line separator
Upon short circuit the part of the line which malfunctions must be separated from
the rest of the line. This is carried out by line separators integrated in the detectors,
manual call points and input/output modules (however, there are detectors without
integrated separator).
A line separator is always integrated in the manual call points and input/output mo-
dules.
According to EN54 a "simple error" can cause the malfunction of up to 32 detectors
(i.e. install a line separator at least after every 32 detectors).
E3M070 Line module "Interactive" (superseded by E3M071)
83
001260_k_en_--.doc
02.2005