Connections - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

36.4

Connections

E3G070
Terminal block
Remote
LED
H1
transm. alarm
Remote transm. fault
LED
H2
(Shown in normal operation)
Alarm horn 1,
LED
H3
monitored control line
LED
H4
Alarm horn 2,
monitored control line
Supply output remote transmis
sion
Module chassis ground
+24V
LED
H5
Inputs / outputs
24V 40mA
LED
H6
LED
H7
LED
H8
LED
H9
LED
H10
LED
H11
0V
switch off
reset
Remote
blocked
transmission
malfunction
C
Plug-in terminals
Supply for
I-Bus modules
F1
Double flat cable header
Data communication
I-Bus modules
Building Technologies
Fire Safety & Security Products
X1
1
Y12
K1
2
X12
3
K2
Y13
X13
4
F6
+
5
24V
F7
-
6
1)
3)
F8
+
7
24V
-
8
F9
F2
+
9
2)
F3
-
10
(connect to
11
chassis ground)
+
12
F4
Q1/I1
-
13
-
14
Q2/I2
Q3/I3
-
15
Q4/I4
-
16
Q5/I5
-
17
Q6/I6
-
18
Q7/I7
-
19
F5
20
Connector
K2
1
1
2
3
4
5
6
K1
1
-
blue
GND
-
2
blue
5V
+
3
green
24V
+
4
red
ST1
1) The indicated polarity at the terminals 5...8 applies to the active state
2) Valid from EP7F the output X1-9, 10 is always monitored. Up to EP5 this output
can be programmed as monitored.
3) Terminate not used horn lines with a 4.75 kΩ.
4.75kΩ
max. 2A
max. 2A
4.75kΩ
to teletransmission unit or to other internal load
Relay / contact must not be outside the
control unit housing
Function output
If "K2" is occupied, the corresponding inputs/outputs on X1
Function input
cannot be used.
Terminals 15...19 can be used as general inputs/outputs,
or
to control the remote transmission equipment
(via plug-in terminals "K2").
to remote transmission equipment
(with cable set Z3I390)
from previous I-Bus modules
to other I-Bus modules
from previous I-Bus modules
to other I-Bus modules
E3G070 Control module "universal"
to remote transmission equipment
max. 24W (60V 1A)
001260_k_en_--.doc
149
02.2005