E3M220 MS5 Adapter

27.1
Overview
27.2
Key data
Operating status of the MS5 detection line
Alarm
AI flashes
Short circuit
< 40 V
Open line
> 232 V
Converter failure
220 V missing
switched on
218 ... 232 V
Reset
0 V
OFF
0 V
switched on
with autom. reset
27.3
Interconnection principle
(220V)
MS5 detectors
Building Technologies
Fire Safety & Security Products
NOTE
The module E3M220 is not CE-conform!
Connection of existing MS5 detectors (220 VDC) to the CS1140 control unit
Converts the signal on the MS5 detection line into a conventional detector signal
(collective 20 V)
Designed for 2 detection lines with bi-directional signal conversion
Only use in combination with the E3M080 line module
Requires a separate supply 24 V
Card format (100 mm x 200 mm)
Number of MS5 detectors per detection line: FES5, DES5, MES5: unlimited
Conversion
–>
–>
–>
<–
<–
<–
<–
Terminal block X10 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
E3M220
Detection
220VDC
line 1
Detection
line 2
FES7.5:
RES5, SES5:
Operating status of the collective line
Alarm
Short circuit
Open line
Open line
switched on
Reset
OFF
Detector test mode with autom. reset
(20V)
24VDC
24VDC
E3M220 MS5 Adapter
max. 25
max. 5
on corresponding line
on corresponding line
on corresponding line
on both detection lines
20 V on corresponding line
0 V on corresponding line
0 V on corresponding line
E3M080
Detection line 1