FAULT TRACING
Fault
Fault ID
Fault name
code
100
1100
Soft fill timeout
101
1101
Feedback supervision
fault (PID1)
105
1105
Feedback supervision
fault (ExtPID)
109
1109
Input pressure super-
vision
1409
111
1315
Temperature fault 1
1316
112
1317
Temperature fault 2
1318
118
1118
AHF Over Temp
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Possible cause
There is a timeout in the
Soft fill function in the PID
controller. The process
value was not achieved in
the time limit.
A pipe that broke can be the
cause.
The PID controller: the feed-
back value is not in the
supervision limits (P3.13.6.2
and P3.13.6.3) and the delay
(P3.13.6.4), if you set the
delay.
The external PID controller:
the feedback value is not in
the supervision limits
(P3.14.4.2 and P3.14.4.3)
and the delay (P3.14.4.4), if
you set the delay.
The supervision signal of the
input pressure (P3.13.9.2) is
lower than the alarm limit
(P3.13.9.7).
The supervision signal of the
input pressure (P3.13.9.2) is
lower than the fault limit
(P3.13.9.8) .
1 or more of the tempera-
ture input signals (set in
P3.9.6.1) is higher than the
alarm limit (P3.9.6.2).
1 or more of the tempera-
ture input signals (set in
P3.9.6.1) is higher than the
fault limit (P3.9.6.3).
1 or more of the tempera-
ture input signals (set in
P3.9.6.5) is higher than the
fault limit (P3.9.6.6).
1 or more of the tempera-
ture input signals (set in
P3.9.6.5) is higher than the
fault limit (P3.9.6.7).
The advanced harmonic fil-
ter function has caused an
overtemperature fault
through a digital input.
VACON · 349
How to correct the fault
Do a check of the process.
Do a check of the parameters in
the menu M3.13.8.
Do a check of the process.
Do a check of the parameter set-
tings, the supervision limits and
the delay.
Do a check of the process.
Do a check of the parameters in
menu M3.13.9.
Do a check of the input pressure
sensor and connections.
Find the cause of the temperature
rise.
Do a check of the temperature
sensor and connections.
If no sensor is connected, make
sure that the temperature input is
hardwired.
See the option board manual for
more data.
Do a check of the advanced har-
monic filter function.