Vacon 100 Industrial Applications Manual page 289

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
Fig. 64: Assigning intervals and timers to time channels is flexible. Every interval and timer has a
parameter with which you can assign them to a time channel.
INTERVALS
Use parameters to give each interval an ON Time and OFF Time. It is the daily active time of
the interval during the days set with parameters From Day and To Day. For example, with the
parameter settings below, the interval is active from 7 am to 9 am from Monday to Friday.
The time channel is like a digital input, but virtual.
ON Time: 07:00:00
OFF Time: 09:00:00
From Day: Monday
To Day: Friday
TIMERS
Use the timers to set a time channel as active for a period with a command from a digital
input or a time channel.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
P AssignToChannel
Interval 1
Interval 2
Interval 3
Interval 4
Interval 5
Timer 1
Timer 2
Timer 3
TimeChannel 1
TimeChannel 2
TimeChannel 3
VACON · 289