VACON · 102
Table 34: Open loop settings
Index
Parameter
P3.1.4.1
U/f Ratio
Field Weakening
P3.1.4.2
Point Frequency
Voltage at Field
P3.1.4.3
Weakening Point
U/f Midpoint Fre-
P3.1.4.4
quency
P3.1.4.5
U/f Midpoint Voltage
Zero Frequency Volt-
P3.1.4.6
age
P3.1.4.7
Flying Start Options
Flying Start Scan
P3.1.4.8
Current
P3.1.4.9
Auto Torque Boost
Torque Boost Motor
P3.1.4.10
Gain
Torque Boost Gener-
P3.1.4.11
ator Gain
M3.1.4.12
I/f Start
5
Min
Max
Unit
0
2
8.00
P3.3.1.2
Hz
10.00
200.00
%
0.00
P3.1.4.2.
Hz
0.0
100.0
%
0.00
40.00
%
0
255
0.0
100.0
%
0
1
0.0
100.0
%
0.0
100.0
%
This menu includes 3 parameters. See the table below.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETERS MENU
Default
ID
Description
0 = Linear
0
108
1 = Squared
2 = Programmable
Varies
602
100.00
603
Varies
604
100.0
605
Varies
606
B0 = Search the shaft
frequency only from
the same direction as
the frequency refer-
ence
B1 = Disable AC scan-
ning
0
1590
B4 = Use the frequency
reference for the initial
guess
B5 = Disable DC pulses
B6 = Flux build with
current control
B7 = Reverse injection
direction
45.0
1610
0 = Disabled
0
109
1 = Enabled
100.0
667
0.0
665