PARAMETER DESCRIPTIONS
Selection
Selection name
number
0
1
WIRING
The connections are different for the parameter values 0 and 1.
SELECTION 0, DISABLED
The drive is directly connected to Motor 1. The other motors are auxiliary motors. They are
connected to the mains by contactors, and controlled by relays of the drive. The autochange
or the interlock logic do not have an effect on Motor 1.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
The drive is always connected to Motor 1. The interlocks do
Disabled
not have an effect on Motor 1. Motor 1 is not included in the
autochange logic.
It is possible to connect the drive to any of the motors in the
Enabled
system. The interlocks have an effect on all the motors. All
the motors are included in the autochange logic.
VACON · 311
Description
10