Vacon 100 Industrial Applications Manual page 258

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

VACON · 258
P3.5.2.1.4 AI1 CUSTOM. MIN (ID 380)
Use this parameter to adjust the range of the analogue input signal between -160% and
160%.
P3.5.2.1.5 AI1 CUSTOM. MAX (ID 381)
Use this parameter to adjust the range of the analogue input signal between -160% and
160%.
For example, you can use the analogue input signal as frequency reference, and set the
parameters P3.5.2.1.4 and P3.5.2.1.5 between 40 and 80%. In these conditions, the frequency
reference changes between the Minimum frequency reference and the Maximum frequency
reference, and the analogue input signal changes between 8 and 16 mA.
Fig. 50: AI1 signal custom. min/max
A. Frequency reference
B. Max freq reference
C. Min freq reference
P3.5.2.1.6 AI1 SIGNAL INVERSION (ID 387)
Use this parameter to invert the analogue input signal.
When the analogue input signal is inverted, the curve of the signal becomes the opposite.
It is possible to use the analogue input signal as frequency reference. The selection of the
value 0 or 1 change scaling of the analogue input signal.
Selection
number
0
10
A
[Hz]
B
C
0%
40%
0 mA
8 mA
E
Selection name
No inversion. The value 0% of the analogue input signal
agrees to the Minimum Frequency Reference. The value
Normal
100% of the the analogue input signal agrees to the Maxi-
mum Frequency Reference.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
80%
100%
16 mA
20 mA
F
D. Analogue input signal
E. AI custom min
F. AI custom max
Description