P3.2.1 REMOTE CONTROL PLACE (ID 172)
Use this parameter to select the remote control place (start/stop).
Use this parameter to change back to remote control from VACON
control panel is broken.
P3.2.2 LOCAL/REMOTE (ID 211)
Use this parameter to switch between the local and remote control places.
Local control place is always keypad control. The remote control place can be I/O or
Fieldbus, depending on the 'Remote Control Place' parameter value.
P3.2.3 KEYPAD STOP BUTTON (ID 114)
Use this parameter to enable the keypad stop button.
When this function is enabled, a press of keypad stop button always stops the drive
(regardless of the control place). When this function is disabled, a press of keypad stop
button stops the drive in local control only.
Selection
number
0
1
P3.2.4 START FUNCTION (ID 505)
Use this parameter to select the type of the start function.
Selection
number
0
1
P3.2.5 STOP FUNCTION (ID 506)
Use this parameter to select the type of the stop function.
Selection
number
0
1
10
Selection name
Yes
The keypad stop button is always enabled.
No
Limited function of the keypad stop button.
Selection name
The drive accelerates from 0 frequency to frequency refer-
Ramping
ence.
The drive detects the actual speed of the motor and acceler-
Flying start
ates from that speed to frequency reference.
Selection name
The motor stops on its inertia. When the stop command is
Coasting
given, the control by the drive stops and the current from the
drive goes to 0.
After the stop command, the speed of the motor is decreased
Ramp
to zero speed according to the deceleration parameters.