Vacon 100 Industrial Applications Manual page 57

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

WIZARDS
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
1
Set a value for P3.1.1.1 Motor Nominal Voltage (so
2
that it agrees with the nameplate of the motor)
Set a value for P3.1.1.2 Motor Nominal Frequency
3
(so that it agrees with the nameplate of the motor)
Set a value for P3.1.1.3 Motor Nominal Speed (so
4
that it agrees with the nameplate of the motor)
Set a value for P3.1.1.4 Motor Nominal Current (so
5
that it agrees with the nameplate of the motor)
If you set Motor Type to Induction Motor, you see the next step. If your selection is PM Motor,
the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes directly to
step 7.
Set a value for P3.1.1.5 Motor Cos Phi (so that it
6
agrees with the nameplate of the motor)
Set a value for P3.3.1.1 Minimum Frequency Refer-
7
ence
Set a value for P3.3.1.2 Maximum Frequency Refer-
8
ence
9
Set a value for P3.4.1.2 Acceleration Time 1
10
Set a value for P3.4.1.3 Deceleration Time 1
Make a selection of a control place (where you give
the start/stop commands)
11
12
Set a value for P3.13.1.4 Process Unit Selection
If your selection is other than %, you see the next steps. If your selection is %, the wizard
goes directly to step 17.
Set a value for P3.13.1.5 Process Unit Min
13
Set a value for P3.13.1.6 Process Unit Max
14
15
Set a value for P3.13.1.7 Process Unit Decimals
Set a value for P3.13.3.3 Feedback 1 Source Selec-
16
tion
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PM motor
Induction motor
Reluctance motor
Range: Varies
Range: 8.00...320.00 Hz
Range: 24...19200 rpm
Range: Varies
Range: 0.30...1.00
Range: 0.00 Hz...P3.3.1.2
Range: P3.3.1.1...320.00 Hz
Range: 0.1...300.0 s
Range: 0.1...300.0 s
I/O Terminal
Fieldbus
Keypad
More than 1 selection
The range depends on the selection in step
12.
The range depends on the selection in step
12.
Range: 0...4
See the table Feedback settings in Chapter
5.13 Group 3.13: PID controller
VACON · 57