PARAMETER DESCRIPTIONS
* = the input is activated.
VALUE 1 SELECTED FOR PARAMETER P3.3.3.1:
You can use the Preset Frequencies 1 to 3 with different sets of active digital inputs. The
number of active inputs tells which one is used.
Table 124: The selection of preset frequencies when P3.3.3.1 = Number of inputs
Activated digital input signal
Preset Freq Sel2
(P3.3.3.12)
*
*
*
*
* = the input is activated.
P3.3.3.10 PRESET FREQUENCY SELECTION 0 (ID 419)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
This parameter is a binary selector for Preset speeds (0-7). See parameters P3.3.3.2 to
P3.3.3.9.
P3.3.3.11 PRESET FREQUENCY SELECTION 1 (ID 420)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
This parameter is a binary selector for Preset speeds (0-7). See parameters P3.3.3.2 to
P3.3.3.9.
P3.3.3.12 PRESET FREQUENCY SELECTION 2 (ID 421)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Preset Freq Sel1
(P3.3.3.11)
*
*
*
*
Preset Freq Sel0
(P3.3.3.10)
*
*
*
*
VACON · 229
Activated frequency
reference
Preset frequency 0
Only if Preset Freq 0 is set
as frequency reference
source with P3.3.3.1.5,
P3.3.1.6, P3.3.1.7 or
P3.3.1.10.
Preset frequency 1
Preset frequency 1
Preset frequency 1
Preset frequency 2
Preset frequency 2
Preset frequency 2
Preset frequency 3
10