VACON · 328
JockeyStopLevel
Jockey Start Level
PID Controller
Wake Up Level
PID Sleep
Jockey Pump Control
(Selected value = PID Sleep)
Jockey Pump Control
(Selected value =
PID Sleep (Level))
Fig. 92: The Jockey pump function
P3.21.2.2 JOCKEY START LEVEL (ID 1675)
Use this parameter to set the level of the PID feedback signal at which the jockey pump
starts when the main pump is in the sleep state.
The jockey pump starts when PID Sleep is active and the PID feedback signal goes below the
level set in this parameter.
NOTE!
This parameter is used only if P3.21.2.1 = 2 PID sleep (level).
P3.21.2.3 JOCKEY STOP LEVEL (ID 1676)
Use this parameter to set the level of the PID feedback signal at which the jockey pump stops
when the main pump is in the sleep state.
The jockey pump stops when PID Sleep is active and the PID feedback signal goes above the
level set in this parameter, or when the PID controller wakes up from sleep mode.
10
PID Feedback
Output Freq
PID Sleep
Delay