PARAMETER DESCRIPTIONS
Output Frequency
Close Frequency Limit
ID1539
Open Frequency Limit
ID1535
Start Command
Open Mech. Brake
Command (Digital output)
Fig. 88: The Mechanical brake function
1. A Start command is given.
2. We recommend that you use start
magnetisation to build rotor flux fast and
to decrease the time when the motor can
produce nominal torque.
3. When the start magnetisation time is
over, the system lets the the frequency
reference go to the open frequency limit.
4. The mechanical brake opens. The
frequency reference stays at the open
frequency limit until the brake
mechanical delay is over, and the correct
brake feedback signal is received.
V
Running
GE
M
Output Frequency
IN
1
P
Open Freq Limit
IN
2
LE
M
Output Frequency
IN
1
P
Close Freq Limit
IN
2
NOT
V
Running
IN
NOT
V
Run Request
IN
V
Fault
LT
M
Motor Current
IN
1
P
Brake Current Limit
IN
2
Fig. 89: The mechanical brake opening logic
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Brake
Mech. Delay
4
3
2
1
5. The output frequency of the drive follows
6. A Stop command is given.
7. The mechanical brake becomes closed
AND
IN
1
IN
2
AND
IN
1
IN
2
OR
IN
1
IN
2
IN
3
5
6
7
the normal frequency reference.
when the output frequency goes below
the close frequency limit.
RS
SET
RESET
NOT
IN
OR
IN
1
IN
2
VACON · 323
I/O
MechanicBrake
I/O
MechanicBrakeInv
10