VACON · 134
Table 71: Temperature input fault 2 settings
Index
Parameter
Temperature Signal
P3.9.6.5
P3.9.6.6
Alarm Limit 2
P3.9.6.7
Fault Limit 2
Fault Limit Response
P3.9.6.8
NOTE!
Temperature input settings are only available if a B8 or BH option board is
installed.
5
Min
Max
0
63
2
-30.0
200.0
-30.0
200.0
0
3
2
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Unit
Default
ID
0
763
°C
130.0
764
°C
155.0
765
2
766
PARAMETERS MENU
Description
B0 = Temperature Sig-
nal 1
B1 = Temperature Sig-
nal 2
B2 = Temperature Sig-
nal 3
B3 = Temperature Sig-
nal 4
B4 = Temperature Sig-
nal 5
B5 = Temperature Sig-
nal 6
0 = No response
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)