Vacon 100 Industrial Applications Manual page 192

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

VACON · 192
Table 121: Fieldbus Control Word
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
9
Value = 0 (FALSE)
Stop request from Fieldbus
Forward direction request
No action
No action
No action
No action
(normal deceleration ramp time)
No action
No action
No action
No action
No action
No action
No action
Reserved
Reserved
Reserved
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
MONITORING VALUE DESCRIPTIONS
Descriptions
Value = 1 (TRUE)
Start request from Fieldbus
Reverse direction request
Reset active faults and alarms (on rising
edge 0=>1)
Force stop mode to Coasting
Force stop mode to Ramping
Force drive to use fast deceleration ramp
time
(1/3 of normal deceleration time)
Freeze drive frequency reference
Force Fieldbus frequency reference to zero
Force drive control place to Fieldbus con-
trol
Force drive reference source to Fieldbus
reference
Jogging Reference 1 activation
NOTE!
This will start the drive.
Jogging Reference 2 activation
NOTE!
This will start the drive.
Activate Quick Stop function
NOTE!
This will stop the drive according to set-
ting in parameter menu M3.9.5.
Reserved
Reserved
Reserved