Vacon 100 Industrial Applications Manual page 251

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
When the contact is CLOSED, the start of the motor is enabled.
NOTE!
The state of the drive remains in 'Not Ready' if the state of this signal is 'opened'.
If the Run Enable signal is used for stopping the drive, the drive will always coast to
stop regardless of the selection in parameter P3.2.5 Stop Function.
P3.5.1.16 RUN INTERLOCK 1 (ID 1041)
Use this parameter to select the digital input signal that prevents to start the drive.
The drive can be ready but start is not possible when the state of the interlock signal is 'open'
(damper interlock).
P3.5.1.17 RUN INTERLOCK 2 (ID 1042)
Use this parameter to select the digital input signal that prevents to start the drive.
The drive can be ready but start is not possible when the state of the interlock signal is 'open'
(damper interlock).
If an interlock is active, the drive cannot start.
You can use this function to prevent the start of the drive when the damper is closed. If you
activate an interlock during the operation of the drive, the drive stops.
P3.5.1.18 MOTOR PREHEAT ON (ID 1044)
Use this parameter to select the digital input signal that activates Motor Preheat function.
The Motor Preheat function feeds DC-current to the motor when the drive is in the stop state.
P3.5.1.19 RAMP 2 SELECTION (ID 408)
Use this parameter to select the digital input signal that selects the ramp time to be used.
P3.5.1.20 ACC/DEC PROHIBIT (ID 415)
Use this parameter to select the digital input signal that prevents the acceleration and the
deceleration of the drive.
No acceleration or deceleration is possible until the contact is open.
P3.5.1.21 PRESET FREQUENCY SELECTION 0 (ID 419)
Use this parameter to set the digital input signal that selects the preset frequencies.
P3.5.1.22 PRESET FREQUENCY SELECTION 1 (ID 420)
Use this parameter to set the digital input signal that selects the preset frequencies.
P3.5.1.23 PRESET FREQUENCY SELECTION 2 (ID 421)
Use this parameter to set the digital input signal that selects the preset frequencies.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
VACON · 251
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

100 x