VACON · 250
PARAMETER DESCRIPTIONS
P3.5.1.5 CONTROL SIGNAL 2 B (ID 424)
Use this parameter to select the digital input signal (Control Signal 2) that starts and stops
the drive when the control place is I/O B.
P3.5.1.6 CONTROL SIGNAL 3 B (ID 435)
Use this parameter to select the digital input signal (Control Signal 3) that starts and stops
the drive when the control place is I/O B.
P3.5.1.7 I/O B CONTROL FORCE (ID 425)
Use this parameter to select the digital input signal that switches the control place from I/O
A to I/O B.
P3.5.1.8 I/O B REFERENCE FORCE (ID 343)
Use this parameter to select the digital input signal that switches the frequency reference
source from I/O A to I/O B.
P3.5.1.9 FIELDBUS CONTROL FORCE (ID 411)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Fieldbus (from I/O A, I/O B or Local control).
P3.5.1.10 KEYPAD CONTROL FORCE (ID 410)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Keypad (from any control place).
P3.5.1.11 EXTERNAL FAULT CLOSE (ID 405)
Use this parameter to select the digital input signal that activates an external fault.
P3.5.1.12 EXTERNAL FAULT OPEN (ID 406)
Use this parameter to select the digital input signal that activates an external fault.
P3.5.1.13 FAULT RESET CLOSE (ID 414)
Use this parameter to select the digital input signal that resets all active faults.
Active faults are reset when the state of the digital input changes from open to closed (rising
edge).
P3.5.1.14 FAULT RESET OPEN (ID 213)
Use this parameter to select the digital input signal that resets all active faults.
Active faults are reset when the state of the digital input changes from closed to open (falling
edge).
P3.5.1.15 RUN ENABLE (ID 407)
Use this parameter to select the digital input signal that sets the drive to Ready state.
When the contact is OPEN, the start of the motor is disabled.