VACON · 252
PARAMETER DESCRIPTIONS
P3.5.1.24 MOTOR POTENTIOMETER UP (ID 418)
Use this parameter to increase the output frequency with a digital input signal.
The motor potentiometer reference INCREASES until the contact is open.
P3.5.1.25 MOTOR POTENTIOMETER DOWN (ID 417)
Use this parameter to decrease the output frequency with a digital input signal.
The motor potentiometer reference DECREASES until the contact is open.
P3.5.1.26 QUICK STOP ACTIVATION (ID 1213)
Use this parameter to select the digital input signal that activates a Quick Stop function. The
Quick Stop function stops the drive regardless of the control place or the state of the control
signals.
P3.5.1.27 TIMER 1 (ID 447)
Use this parameter to select the digital input signal that starts the timer.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.28 TIMER 2 (ID 448)
Use this parameter to select the digital input signal that starts the timer.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.29 TIMER 3 (ID 449)
Use this parameter to select the digital input signal that starts the timer.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.30 PID SETPOINT BOOST (ID 1046)
Use this parameter to select the digital input signal that activates the boost for the PID
setpoint value.
The timer starts when this signal is deactivated (falling edge). The output is deactivated when
the time defined in the duration parameter has elapsed.
P3.5.1.31 PID SETPOINT SELECTION (ID 1047)
Use this parameter to set the digital input signal that selects the PID setpoint value to be
used.
P3.5.1.32 EXTERNAL PID START SIGNAL (ID 1049)
Use this parameter to select the digital input signal that starts and stops the external PID
controller.