Vacon 100 Industrial Applications Manual page 133

Ac drives
Hide thumbs Also See for 100 Industrial:
Table of Contents

Advertisement

PARAMETERS MENU
Table 70: Temperature input fault 1 settings
Index
Parameter
Temperature Signal
P3.9.6.1
1
P3.9.6.2
Alarm Limit 1
P3.9.6.3
Fault Limit 1
Fault Limit Response
P3.9.6.4
1
NOTE!
Temperature input settings are only available if a B8 or BH option board is
installed.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
Unit
0
63
-30.0
200.0
°C
-30.0
200.0
°C
0
3
Default
ID
Description
B0 = Temperature Sig-
nal 1
B1 = Temperature Sig-
nal 2
B2 = Temperature Sig-
nal 3
0
739
B3 = Temperature Sig-
nal 4
B4 = Temperature Sig-
nal 5
B5 = Temperature Sig-
nal 6
130.0
741
155.0
742
0 = No response
1 = Alarm
2 = Fault (Stop accord-
2
740
ing to stop mode)
3 = Fault (Stop by
coasting)
VACON · 133
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

100 x

Table of Contents