Selected Motor; Drive Fault Auto Reset - KEB COMBIVERT F5 Instruction Manual

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Parameter Description - Basic Set Up

Selected motor

Drive fault auto reset

This parameter displays the current mode of operation, open or closed
loop, geared or gearless, induction motor, synchronous motor. The
parameter is read only.
Possible displays:
ICLSd
= Closed loop induction
I9LSS
= Closed loop induction gearless
PCLSd
= Closed loop permanent magnet
P9LSS
= Closed loop permanent magnet gearless
With LF. 5 all drive faults can be automatically reset.
The number adjusted in this parameter determines how many times
per hour the elevator drive will automatically reset faults. Before
resetting the fault, the drive will wait 4 seconds to allow everything
to stop or stabilize. It is not fault specifi c, so with the default setting
of 5, if the drive experiences 6 different faults in one hour the unit
will latch the last fault and not reset. See parameter LF.98 for fault
history information.
Unit:
1
Value range:
0...10
Default setting:
5
Note: a setting of "0"
means no fault resets.
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents