10.2

Electromagnetic compatibility

Definition
Electromagnetic compatibility is the ability of an electrical apparatus to function in a
satisfactory manner in its electromagnetic environment without affecting this environment.
An I/O device of the ET 200AL distributed I/O system fulfills the requirements of the EMC law
of the European Union. The requirement for this is that an I/O device of the ET 200AL
distributed I/O system meets the specifications and guidelines for electrical configuration.
Pulse-shaped disturbance variables
The table below shows the electromagnetic compatibility of the distributed I/O systems
compared to pulse-shaped disturbance variables.
Table 10- 1
Pulse-shaped disturbance variable
Electrostatic discharge according to
IEC 61000-4-2.
Burst pulses (rapid transient disturb-
ance values) according to IEC 61000-
4-4.
High-energy surge according to IEC 61000-4-5.
Distributed I/O system
System Manual, 08/2019, A5E31861578-AG
Pulse-shaped disturbance variables
Asymmetrical coupling
Symmetrical coupling
10.2 Electromagnetic compatibility
Tested with
Air discharge: ±8 kV
Contact discharge: ±4 kV
±2 kV (power supply cable)
±2 kV (PROFIBUS-/PROFINET line)
±1 kV (signal line <30 m)
±1 kV (ET-Connection)
±2 kV (24 V DC supply cable)
with protective element
±0.5 kV (24 V DC supply cable)
without protective element
±2 kV (PROFIBUS/PROFINET line)
without protective element
±1 kV (24 V DC supply cable)
with protective element
±0.5 kV (24 V DC supply cable)
without protective element
Technical specifications
Corresponds to
degree of sever-
ity
3
2
3
4
3
3
3
1
3
3
2