Technical specifications

9.2 Electromagnetic compatibility

9.2
Electromagnetic compatibility
Definition
The electromagnetic compatibility (EMC) is the ability of an electrical device to function in its
electromagnetic environment without influencing this environment.
EMC requirements fulfilled
The ET 200SP HA distributed I/O system also fulfills the requirements of the EMC directive for
the European domestic market.
Requirement
You must ensure that the configuration of the ET 200SP HA corresponds to the specifications
and guidelines for electrical setup.
EMC in accordance with NE21
The ET 200SP HA distributed I/O system fulfills the EMC specifications according to NAMUR
directive NE21.
Pulse-shaped disturbance variables
The following table shows the electromagnetic compatibility of the ET 200SP HA distributed IO
system with pulse-shaped interference.
Table 9-2
Disturbance variable
Electrostatic discharge in accordance
with IEC 61000‑4‑2
Burst pulses (fast transients) in accord‐
ance with IEC 61000‑4‑4
for the frequencies 5 kHz and 100 kHz
High-energy single pulse (surge) in accordance with IEC 61000‑4‑5
Basic information about the external protective circuit, see the " Designing interference-free controllers
(https://support.industry.siemens.com/cs/ww/en/view/59193566)" function manual.
● Signals
● Signals (with external protection)
● Signals directly in AC network
● DC supply
● DC supply (with external protection) ±2 kV asymmetrical (line to ground)
138
Pulse-shaped disturbance variables
Tested with
Air discharge: ±8 kV
Contact discharge: ±6 kV
±2 kV (power supply line)
±2 kV (signal line)
±1 kV asymmetrical (line to ground)
±2 kV unbalanced (line to ground)
±1 kV balanced (line to line)
±2 kV unbalanced (line to ground)
±1 kV balanced (line to line)
±1 kV unbalanced (line to ground)
±0.5 kV balanced (line to line)
±1 kV balanced (line to line)
System Manual, 08/2019, A5E39261167-AD
Corresponds
to degree of
severity
3
3
3
3
2
3
3
2
3
ET 200SP HA Distributed I/O system