4.4

Basic configuration of a Rosemount 2410 Tank Hub

This is a general description of how to configure a Rosemount 2410 Tank Hub. The Rosemount Tank
Gauging System Configuration Manual (Document no. 00809-0300-5100) provides a detailed description
of how to use the Rosemount TankMaster WinSetup program as a configuration tool for the Rosemount
2410.
Communication
Depending on the particular system configuration, a Rosemount 2410 Tank Hub may communicate
directly with a host computer or via a Rosemount 2460 System Hub.
In case the Rosemount 2410 is connected to a Rosemount 2460 System Hub, you will have to specify
which communication protocol channel to be used.
The Rosemount 2410 has default Modbus
recommended address range. The Modbus address must match the address specified in the Rosemount
2460's tank database.
The Rosemount 2410 Tank Hub can be used in a WirelessHART system by connecting an Emerson
Wireless THUM
system via an Emerson Wireless Gateway.
Tank database
The Rosemount 2410 has a tank database that maps field devices to tanks. It also stores Modbus
addresses of level gauges and auxiliary tank devices (ATD) such as the Rosemount 2240S Multi-input
Temperature Transmitter. The Modbus addresses are used for communication with Rosemount 2460
System Hub and host computers.
Device tags
For each tank, device tags are specified for the level gauge and the auxiliary tank devices (ATD). ATD
devices include all instruments on the tank except the level gauge. Device tags are used as identifiers in
TankMaster.
Integral display
The Rosemount 2410 can be configured to present measurement data on the optional integral display.
The display alternates between the selected items at a rate given by the Display Toggle Time parameter.
Measurement data such as Level, Level Rate, Free Water Level and many other tank variables can be
displayed.
Measurement units for Level, Level Rate, Volume, Temperature, Density, and Pressure can be specified
regardless of which units are used for presentation in, for example, the TankMaster programs.
Configuration
Adapter. The THUM adapter allows the Rosemount 2410 to communicate with a host
®
adress=247. The address should be changed to the
Configuration
March 2017
61