Service and Troubleshooting
March 2017
Symptom
No communication with
one or more devices on
the Tankbus
98
Possible cause
Cables are too long
Software or hardware failure
00809-0100-2410, Rev DA
Action
Check that the input voltage on the device terminals
is 9 V or more (see section
Check diagnostics information, see
on page
84.
Check Device Status input register, see
status" on page
102.
Contact Emerson Automation
Solutions/Rosemount Tank Gauging service
department.
Reference Manual
"Tankbus" on page
29).
"Diagnostics"
"Device
Service and Troubleshooting