11Testing The Relays - Emerson Rosemount 2410 Reference Manual

Tank hub
Hide thumbs Also See for Rosemount 2410:
Table of Contents

Advertisement

Reference Manual
00809-0100-2410, Rev DA
6.2.11
Testing the relays
The Manual Control of Relay function lets you manually open or close the Rosemount 2410 Tank Hub
built-in relays in order to verify the relay function. After the specified Safety Reset Time the relay
automatically returns to normal mode.
To change relay state by using the TankMaster WinSetup program do the following:
1. In the TankMaster WinSetup workspace select the Rosemount 2410 icon.
2. Click the right mouse button and choose Manual Control Relay.
3. Select the virtual relay functions to be tested; Virtual Relay 1, Virtual Relay 2, etc.
Up to ten virtual relay functions can be configured for a Rosemount 2410 Tank Hub. See
configuration in Winsetup" on page 137
4. Specify a Safety Reset Time. This value specifies the time period for the relay to stay in the test state.
When the specified period of time has elapsed, the relay automatically returns to the original state.
The relay will reset even if communication with the TankMaster PC would fail.
5. Choose the desired Manual Relay State. Available options are Alarm, Normal, and Toggle.
6. Click the Set button. Now the selected relay changes state for the specified number of seconds and
then returns to the previous state.
Service and Troubleshooting
Service and Troubleshooting
and
"Relay output" on page 140
March 2017
"Advanced
for more information.