example an instrument sets the output current in alarm mode to 3.8 mA, you should set the lower error
limit to 3.8 or higher.
13.In the Analog Input Values pane, verify that Status is OK and that the expected measurement results
appear in the Value and Current fields.
14.Select the Advanced Parameter Source Configuration tab:
15.Map the Analog Input to the desired tank parameter. In the example above it is mapped to Vapor
Pressure.
16.Select Analog Input as Source Device Type to make sure that the 4 - 20 mA signal of the connected
instrument is mapped to the selected parameter.
Advanced Configuration
Advanced Configuration