Advanced Configuration
March 2017
C.3

Primary bus

The Rosemount 2410 has a Primary Bus which is used for communication with a Rosemount 2460
System Hub. It may also be connected directly to a control room PC.
The Primary Bus supports TRL2, RS485, and other communication buses. The Rosemount 2410
automatically detects what modem is installed in the Primary Bus slot and communication parameters
are set accordingly. For some modem types (such as RS485) the non standard option allows you to
configure communication with other protocols than the standard Modbus
To open the Primary Bus window:
1. In the WinSetup workspace click the right mouse button on the Rosemount 2410 icon.
2. Choose the Properties option to open the 2410 Tank Hub window.
3. Select the Configuration tab.
4. Click the Primary Bus button. The Primary Bus Configuration window lets you configure protocol,
baudrate, and other communication parameters when the standard settings are not appropriate.
To change communication parameters:
1. In the Configuration drop-down menu, change from Standard to Non Standard.
2. Choose the desired Protocol.
3. Choose appropriate communication parameter values for Baudrate, Databits, Parity, and Stop Bits.
4. Click Apply to store the current configuration, or click OK to store the configuration and close the
Primary Bus Configuration window.