Reference Manual
00809-0100-2410, Rev DA
6.2.13
Loading the default database
The various configuration parameters of the Rosemount 2410 Tank Hub is stored in a Holding Register
database. The Holding Register factory setting is stored in the default database. TankMaster WinSetup
offers the option to load the default database. This may be useful if, for example, you would like to try out
new database settings and then be able to reload the original factory settings.
In case error messages appear or other problems occur concerning the database, troubleshooting the
cause of these problems is recommended before loading the default database.
It is recommended that the current database is backed up before the Default Database is loaded. See
"Configuration backup" on page 82
Note
The communication address of the device remains unaltered when the default database is loaded.
Note
When the default database is loaded to the Rosemount 2410 Tank Hub, measurement units are reset to
Metric units.
To load the default database:
1. Select the desired device icon in the TankMaster WinSetup workspace window.
2. Click the right mouse button and choose the View Holding Register option.
3. Choose the All option and type 65510 in the Start Register input field. Type the desired number of
registers to be displayed in the Number of Registers field and click the Read button.
4. Type 65510 in the Value input field.
5. Click the Apply button to load the default database.
6. Finish by clicking the Close button.
7. Verify that measurement units are compatible with the current host system configuration.
Service and Troubleshooting
for information on how to save the current database.
Service and Troubleshooting
March 2017
93