Service and Troubleshooting
March 2017
a. In the TankMaster WinSetup workspace window select the Devices folder.
b. Click the right mouse button and choose the Program All option to open the Program Devices
c. From the Available Devices pane choose a Rosemount 2410 Tank Hub to be programmed and
d. Repeat for each device to be programmed.
7. Click the Browse button to locate the flash program file. A flash file is identified by file extension
*.cry. For a Rosemount 2410, a flash file name may typically look like: 2410_APPL_xxx_yy.cry, where
"x" and "y" indicate software version.
8. In the Program Devices window click the Start Programming button to open the Start Device
Programming window:
9. Click the Start Programming button to activate device programming.
10.Programming may take up to two hours for a Rosemount 2410 connected to a TankMaster PC via a
2460 System Hub. The programming procedure will continue with one device after the other until all
Tank Hubs selected in the Program Devices window are upgraded.
By connecting a Rosemount 2410 directly to a host computer, and using the RS485 Modbus
protocol at a maximum baud rate of 38400, programming time may be reduced to 5 to 10 minutes
(see
11.The Rosemount 2410 operates as normal during the reprogramming procedure. Once programming
is finished, the tank hub will automatically perform a restart indicated by "WAIT" on the integral
display for a couple of minutes.
86
window:
click the Move button.
Use the Remove button if you want to change the list of devices to be programmed.
"Primary bus" on page 138
for information on how to configure the Primary Bus).
Reference Manual
00809-0100-2410, Rev DA
®
Service and Troubleshooting