Product Certifications
March 2017
B.4 North America
E5
USA Explosion-proof
Certificate: FM16US0123X
Standards: FM Class 3600 – 2011,
FM Class 3610 – 2010,
FM Class 3615 – 2006,
FM Class 3810 – 2005,
NEMA 250 – 2003,
ANSI/IEC 60529 – 2004,
ANSI/ISA 60079-0 – 2009,
ANSI/ISA 60079-11 Ed 5.1 – 2011,
ANSI/ISA 60079-27 – 2006
Ex marking
Comm. Bus
Ex d e [ib] IIB T4
FISCO
HART/ 4-20mA
Ex d e [ia IIC] IIB T4
Active
HART/ 4-20mA
Ex d e ib IIB T4
Passive
Ex d e [ib] IIB T4
Fieldbus
Special Conditions for Safe Use (X):
1. The flamepaths of the equipment are not intended to be repaired. Consult the manufacturer if repair of the flamepath joints is
necessary.
120
Ui
Ii
Pi
Ci
μ
V
mA
W
F
-
-
-
-
-
-
-
-
30
300
1
0
-
-
-
-
Markings: AIS/I/1/CD
XP-AIS/I/1/CD/T4 Ta = -50°C to +70°C
DIP/II,III/1/EFG/T4 Ta = -50°C to +70°C;
I/1/Ex d e [ib] IIB T4 Ta = -50°C to +70°C
I/1 [0]/Ex d e [ia IIC] IIB T4 Ta = -50°C to +70°C
I/1/Ex d e ib IIB T4 Ta = -50°C to +70°C
Type 4X; IP66; IP67
Li
Uo
Io
Po
mH
V
mA
W
-
15
354
5.32
-
23.1
95.3
0.55
0
-
-
-
-
15
200
3
Reference Manual
00809-0100-2410, Rev DA
Co
Lo
Group
μ
F
mH
-
-
IIB
0.14
3.9
IIC
1.0
15
IIB
3.67
33
IIA
-
-
IIB
1.99
143
IIB
Product Certifications