Error messages

Error messages may be displayed on the Rosemount 2410 integral display and in the Rosemount
Tankmaster program. You also have the option to view Input Register 1002 for an overview of active
device errors (see
information on how to view diagnostics and various Input registers with TankMaster WinSetup).
For each error message that may appear in Input register 1002, detailed information can be found in
Input registers 6100 to 6124 as shown in
Table 6-6. Error message descriptions
RAM error
FPROM error
HREG error
SW error
Service and Troubleshooting
"Diagnostics" on page 84
Message
or
"Viewing Input and Holding registers" on page 78
Table
6-6.
Description
Input register no. 6100.
A gauge data memory (RAM) error
has been detected during the startup
tests. Note: this automatically resets
the gauge.
Input register no. 6102:
Bit 0: checksum
Bit 1: Application version
Bit 2: Application checksum
Input register no. 6104:
Bit 0: Checksum
Bit 1: Limit
Bit 2: Version
Bit 3: Read
Bit 4: Write
Input register no. 6106:
Bit 0: Undefined SW Error
Bit 1: Task Not Running
Bit 2: Out of stack space
Bit 3: Unused RAM access
Bit 4: Divide by zero
Bit 5: Reset Counter Overflow
Bit 15: Simulated SW Error
Service and Troubleshooting
Action
Contact Emerson Automation
Solutions/Rosemount Tank Gauging
service department.
Probably a checksum error in the
application software. Try to
reprogram the Rosemount 2410.
Probably a checksum error caused by
power failure between a
configuration change and CRC
update. Reset to factory
configuration (see
"Loading the
default database" on page
reconfigure the Rosemount 2410.
Use the Reset command before
checking the error status.
The Rosemount 2410 software is
having trouble running stable.
1. Switch off the power to the tank
hub for at least one minute.
2. Switch power on again.
If the problem persists, contact
Emerson Automation
Solutions/Rosemount Tank Gauging
service department.
March 2017
for
93) and
105